ALPHABETIC REFERENCE
Internal Parameters
74-5577–33 (US)
EN2B-0184 GE51 R0518 (Europe)
h = Current hourly consumption
ph = Past hourly consumption
d = Current daily consumption
pd = Past daily consumption
pmo = Past monthly consumption
The outputs require creation of five user addresses of the type pseudo analog.
P1 = Displ_current_hour* (Current hourly consumption)
P2 = Displ_past_hour* = (Past hourly consumption)
P3 = Displ_current_day* = (Current daily consumption)
P4 = Displ_past_day* = (Past daily consumption)
P5 = Displ_current_mon* = (Current monthly consumption)
P6 = Displ_past_mon* = (Past monthy consumption)
P7 = Displ_total* = (Total consumption since startup)
P8 = Basic_value = (Counter value at totalizer start point)
P9 = Internal_parameter = (No user entry)
P10 = Initialization_con** = (Initialization of total consumption)
P11 = Internal_parameter = (No user entry)
P12 = Version_number*
P13 = XFM_number*
* Read-only parameters
** Set P10 to 1 to cause the value of P7 to be reset to the value of P8 (the basic value)
90