Honeywell EXCEL 5000 User Manual page 165

Open system control icons
Hide thumbs Also See for EXCEL 5000:
Table of Contents

Advertisement

EXCEL CARE CONTROL ICONS
Internal Parameters
Minimum pre-heat time
(with room sensor) P1
Maximum pre-heat time
No room sensor
Optimum stop outdoor air
temperature low limit P4
Pre-heat time at 0 °C
outdoor air temperature
(without room sensor) P5
Optimum stop factor (with
room sensor) P6
Room comfort zone optimum stop P7
3
4
5
6
7
8
RmCtrl (YD5) = indicates room control mode.
• 0: No room control
• 1: Room control during optimum start
• 2/3: Room control after optimum start
• 8 minimum room temperature protection or control
Number type: Whole number, Unit: Minutes
Default: 60 min, Range: 0 through 1440 min
P2
Number type: Whole number, Unit: Minutes
Default: 2880 min, Range: > =0
constant P3
Number type: Decimal, Unit: Degrees Celsius
Default: 10°C, Range: 0 through 20 °C
Number type: Decimal, Unit: Degrees Celsius
Default: 0 °C, Range: 10 through +15 °C
Number type: Whole number, Unit: Minutes
Default: 120 min, Range: >=0
Number type: Whole number, Unit: Minutes/ Kelvin
Default: 10 min/ K Degree, Range: 0 through 55 min/ Kelvin
Number type: Whole number, Unit: Kelvin
Default: 2 K, Range: 0 through 10 K
Optimum start without room sensor
Optimum start due to minimum preheat time without room
sensor
Optimum start with room sensor
Optimum start due to minimum preheat time with room sensor
Optimum stop without room sensor
Optimum stop with room sensor
167
ALPHABETIC REFERENCE
Excel Web II
74-5577–33 (US)
EN2B-0184 GE51 R0518 (Europe)