ALPHABETIC REFERENCE
XFM Outputs
74-5577–33 (US)
EN2B-0184 GE51 R0518 (Europe)
ramp.csd
UP-DOWN RAMP
ratio.csd
RATIO
xfm_34.csd
Totalizer
xfm_35.csd,
xfm_36-1.csd
Power Demand
Using XFMs
When using XFMs in custom control strategies, keep in mind the following notes
about the unique behavior of the underlying XFM software.
CAUTION
Mixing XFMs with other control icons in a control strategy loop results in the
creation of individual submodules for each XFM. Software places all other icon
control functions (and their subsequent parameters) in the Main Module. Main
Module parameters are limited to a maximum of 128, so combinations of
complex control strategies that contain XFMs may be limited by this parameter
restriction.
You must connect all XFM inputs and outputs to a valid user address, even if you
are not using the output in the control strategy. Valid user addresses can include
flag points (internal user addresses) or pseudopoints.
As an input varies between a minimum value and a maximum
value, the output follows on a time-delayed basis.
As an input varies between two input bounds, output varies
between two output bounds. Output can be bounded or
unbounded.
Totalizer module that:
1.
Logs and displays current hourly and daily energy usage.
2.
Logs and displays past hourly and daily energy usage.
3.
Logs the total energy usage from program start-up or
current monthly usage.
Energy usage can include electrical current, water, gas, or
heat. This function eliminates the need to connect an external
frequency counter.
The power demand control functions measure the energy
consumption of the plant electrical units. They then calculate
current power consumption, compare it to a power limit, and
decide which load(s) to switch on or off.