Honeywell EXCEL 5000 User Manual page 93

Open system control icons
Hide thumbs Also See for EXCEL 5000:
Table of Contents

Advertisement

EXCEL CARE CONTROL ICONS
XFM 35 Internal Parameters
Parameter
Number
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
The XFM 35 internal parameters dialog box lists parameters that control program
functions. Later sections describe how to use these parameters depending on
operation desired. The table following the dialog box summarizes parameter types,
functions, default values, setting range, and engineering units. (The dialog box
values and engineering units are not necessarily the defaults.)
Type
Display
Moment_Power_Cons (current power
consumption)
Display
Remaining_Rest_Tim(e) (not for Sliding Window)
Display
Remaining_Work (not for Sliding Window)
Display
Possible_Power (with constant power
consumption)
Comm.
Max(imum)_Switch_On_P(ower)
Comm.
Safety_Margin
Comm.
Hysteresis_Switch (for power)
Comm.
Test( Board )/Param(eter)_ Change (Set to 1
when changing any other parameter)
Comm.
Measurem_Procedure (algorithm type: 1 = Sliding
Window; 2 = Ideal Curve; 3 = Extrapolation)
Comm.
Measurement_Interv(al/window size)
Comm.
Freeze_Time (not for sliding window)
Comm.
Switch-On_Wait_Tim(e)
Comm.
(Power) Limit_1 (for ID___Tariff=0)
Comm.
(Power) Limit_2 (for ID___Tariff=1)
Progr.
Prio/Rotat(0/1)_P1 (sequential or rotational load
shed method for priority 1 groups) Sequential=0
Progr.
Prio/Rotat(0/1)_P1 (sequential or rotational load
shed method for priority 2 groups) Sequential=0
Brief Description
95
ALPHABETIC REFERENCE
Setting
Default
Range
Value
Unit
none
none
none
none
min
none
none
kWh
none
none
1-1000
10
0-1000
0
0-1000
0.5
0/1/2/3
2
Integer
1/2/3
3
Integer
1-7200
15
min
30-300
180
sec
0-240
120
sec
0-10 6
10000
0-10 6
10000
0 or 1
0
Integer
0 or 1
0
Integer
74-5577–33 (US)
EN2B-0184 GE51 R0518 (Europe)
kW
kW
kW
kW
kW
kW
kW