ALPHABETIC REFERENCE
Comfort range P3
Minimum cooling
Maximum heating
Minimum mixed air
ZEB/Load reset mode P8
Room humidity limit P10
Heating reset range P11
Cooling reset range P12
Mixed air reset range P13
humidity sensor type (radio button) P4
humidity sensor (radio button) P9
Parameter Number
Descriptions
:
74-5577–33 (US)
EN2B-0184 GE51 R0518 (Europe)
Number type: decimal, Unit: Deg
Default: 4.0 Deg, Range: 0 through 30
This value defines the width of the heating, cooling, and zero energy ranges. The
width of each range is two times this value. All ranges are equally wide. The zero
energy range is located symmetrically around the setpoint X5. The cooling range is
located immediately above the upper limit of the zero energy range. The heating
range is located immediately below the lower limit. See the Operation diagram later
in this section.
setpoint P5
Number type: decimal, Unit: Degrees
Default: 13, Range: 5 through 27
This field is intended for use as the lowest allowable discharge air setpoint during
cooling, that is, the maximum cooling effect.
setpoint P6
Number type: decimal, Unit: Degrees
Default: 35, Range:10 through 60
This field is intended for use as the highest allowable discharge air setpoint during
heating, that is, the maximum heating effect.
setpoint P7
Number type: decimal, Unit: Degrees
Default: 13, Range: 5 through 32
Lowest mixed air, or discharge air setpoint while in the ZEB range.
1 = ZEB (Zero energy band)
2 = Heating control setpoint
3 = Cooling control setpoint
4 = Heating and cooling control setpoint
Number type: decimal, Unit: Percent
Default: 65 percent rh, Range: 40 through 80 percent rh
Number type: decimal, Unit: Deg
Default: 15, Range: 15 through 25
Number type: decimal, Unit: Deg
Default: 6K, Range: 0 through 20
Number type: decimal, Unit: Deg
Default: 7, Range: 0 through 25
Selection of the type of the humidity sensor (relative or absolute humidity).
Range: 0 through 1, default: 1 (1= relative, 0= absolute)
Selection whether or not a humidity sensor is connected.
Range: 0 through 1, default: 1 (1= with sensor, 0= no sensor)
P3 Comfort range
P4 Relative (1) or absolute (0) humidity sensor
P5 Minimum cooling setpoint
P6 Maximum heating setpoint
P7 Minimum mixed air setpoint
P8 ZEB/Load reset mode:
P9 With (1) or without (0) humidity sensor
P10 Room humidity limit
P11 Heating reset range
P12 Cooling reset range
P13 Mixed air reset range
P14 Setpoint X5, if X5 is a parameter (not for Excel Web / Excel Web II).
1=ZEB
2=Heating control setpoint
3=Cooling control setpoint
4=Heating and cooling control setpoint