ALPHABETIC REFERENCE
I/O Dialog Box
Internal Parameters
Parameter Number
Descriptions
74-5577–33 (US)
EN2B-0184 GE51 R0518 (Europe)
Function
Switch an analog value depending on a digital value.
For example:
If XD1 = 1, set output Y to X2.
If XD1 = 0, set output Y to X3.
Formula
Y = X2, if XD1 = 1.
Y = X3, if XD1 = 0.
Inputs
One digital input (XD1).
Two analog inputs (X2 and X3).
You can enter the two analog inputs as parameters (engineering unit index number
and value for each parameter).
Output
One analog output (Y).
None.
P3 X2 if X2 is not connected with a point.
P4 X3 if X3 is not connected with a point. If X2 is connected with a point, X3 is
numbered parameter 4.
Example
See the Examples chapter in this manual for applications that use the SWI control
icon.
Also see the Digital Conversion note in the Mathematical Editor (MAT) section. You
can use SWI to convert a digital point to analog values for use in a mathematical
formula.
24
EXCEL CARE CONTROL ICONS
Analog Switch / SWI