EXCEL CARE CONTROL ICONS
Minimum pre-heat time
(with room sensor) P4
Maximum pre-heat time
(only Excel Web / Excel Web II)
Maximum pre-heat setpoint
(with room sensor) P8
No room sensor
Optimum stop outdoor air
temperature low limit P7
Pre-heat time at 0C
outdoor air temperature
(with room sensor)
Optimum stop (with
room sensor) P9
Number type: Whole number, Unit: Minutes
Default: 120 min, Range: 0 through 1440 min
Number type: Whole number, Unit: Minutes
Default: 2880 min, Range: > 0
Number type: Decimal, Unit: Degrees Fahrenheit
Default: 175F (80C), Range: 32 through 302F (0 through 150C)
constant P6
Number type: Decimal, Unit: F Deg
Default: 20 F Deg (10K), Range: 0 through 36 F Deg (0 through 20K)
Number type: Decimal, Unit: Degrees Fahrenheit
Default: 32F (0C), Range: 14 through 59F (-10 through +15C)
Number type: Whole number, Unit: Minutes
Default: 120 min, Range: 0 through 1440 min
Number type: Whole number, Unit: Minutes/F Deg
Default: 20min/F Deg, Range: 0 through 110 min/F Deg