EXCEL CARE CONTROL ICONS
ALPHABETIC REFERENCE
Setup for the internal parameters:
Parameter Availability
Only the Y parameters for SEQ are available in the controller after program
installation.
Negative Values
Use the Ratio (RAMP) function to generate negative values.
SET (Excel Web / Excel Web II)
Functions
Legacy RACL function: Set the output depending on the comparison of the inputs.
Formula
Y=FALSE (0) if A < B
Y=TRUE (1) if A > B
Y is not changed if A = B.
I/O Dialog Box
Inputs
Two analog inputs (A and B).
Outputs
One output (Y) result of the comparison A with B.
Internal Parameter
None.