Honeywell EXCEL 5000 User Manual page 99

Open system control icons
Hide thumbs Also See for EXCEL 5000:
Table of Contents

Advertisement

EXCEL CARE CONTROL ICONS
Parameter
Number
1
2
3
4
6
9
10
13
14
Select the Extrapolation algorithm by setting Parameter P9 to the value 3.
A safety margin parameter (P6) provides a secure margin between the current
power peak (Parameter P1) and the possible power (Parameter P4).
The internal user address IA___Energy_Intv indicates current energy consumed
(equal to Z 7 - Z 0 in the previous diagram) during the measurement interval. The
General Functions subsection explains the other internal user addresses and
parameters used in this algorithm.
The following table lists parameters used for the extrapolation algorithm.
Type
Brief Description
Display
Current Power Consumption
Display
Remaining Rest Time
Display
Remaining Work
Display
Possible Power with constant
Power Consumption
Comm.
Safety Margin
Comm.
Measurement Algorithm
3=Extrapolation
Comm.
Measurement Interval/Window Size
Comm.
Power Limit 1
Comm.
Power Limit 2
101
ALPHABETIC REFERENCE
Setting
Default
Range
Value
none
none
none
none
none
none
none
none
0-1000
0
1/2/3
3
Integer
1-7200
15
0-10 6
10000
0-10 6
10000
74-5577–33 (US)
EN2B-0184 GE51 R0518 (Europe)
Unit
kW
min
kWh
kW
kW
min
kW
kW

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents