How to Programme
5-12 Terminal 27 Digital Input
Option: Function:
Select the function from the available digital input
range.
No operation
Reset
Coast inverse
4
4
Coast and reset inverse
Quick stop inverse
DC-brake inverse
Stop inverse
Start
Latched start
Reversing
Start reversing
Enable start forward
Enable start reverse
Jog
Preset ref bit 0
Preset ref bit 1
Preset ref bit 2
Freeze reference
Freeze output
Speed up
Speed down
Set-up select bit 0
Set-up select bit 1
Catch up
Slow down
Pulse input
Ramp bit 0
Ramp bit 1
Mains failure inverse
DigiPot Increase
DigiPot Decrease
DigiPot Clear
Reset Counter A
Reset Counter B
1-29 Automatic Motor Adaptation (AMA)
Option:
58
VLT
Operating Instructions High Power
Function:
The AMA function optimizes dynamic motor
performance by automatically optimizing the
advanced motor parameters (par. 1-30 to par.
1-35) at motor standstill.
Activate the AMA function by pressing [Hand
on] after selecting [1] Enable complete AMA or
[2] Enable reduced AMA. See also the section
Automatic Motor Adaptation. After a normal
sequence, the display will read: "Press [OK] to
finish AMA". After pressing [OK], the frequency
converter is ready for operation.
MG34Q202 - VLT
®
Automation Drive FC 300 12-Pulse
1-29 Automatic Motor Adaptation (AMA)
Option:
[0]
OFF
*
[0]
[1]
Enable
[1]
complete
[2]
AMA
[3]
[4]
[5]
[6]
[8]
[9]
[10]
[2]
Enable
reduced
[11]
AMA
[12]
[13]
[14]
Note:
[16]
For the best adaptation of the frequency
[17]
converter, run AMA on a cold motor.
[18]
AMA cannot be performed while the motor is
[19]
running.
[20]
AMA cannot be performed on permanent magnet
[21]
motors.
[22]
[23]
It is important to set motor parameter group 1-2*
[24]
correctly, since these form part of the AMA algorithm. An
[28]
AMA must be performed to achieve optimum dynamic
[29]
motor performance. It may take up to 10 min, depending
[32]
on the power rating of the motor.
[34]
[35]
Avoid generating external torque during AMA.
[36]
[55]
If one of the settings in parameter group 1-2* is changed,
[56]
par. 1-30 to par. 1-39, the advanced motor parameters, will
[57]
return to default setting.
[62]
[65]
3-02 Minimum Reference
Range:
Application dependent
3-03 Maximum Reference
Range:
Application
dependent
*
®
is a registered Danfoss trademark
Function:
This parameter cannot be adjusted while the
motor is running.
Performs AMA of the stator resistance R
rotor resistance R
, the stator leakage
r
reactance X
, the rotor leakage reactance X
1
and the main reactance X
.
h
FC 301: The complete AMA does not include
X
measurement for FC 301. Instead, the X
h
value is determined from the motor database.
1-35 Main Reactance (Xh) may be adjusted to
obtain optimal start performance.
Performs a reduced AMA of the stator
resistance R
in the system only. Select this
s
option if an LC filter is used between the
frequency converter and the motor.
[Application dependant]
*
Function:
[Application
Enter the Maximum Reference. The
dependant]
Maximum Reference is the highest
value obtainable by summing all
references.
The Maximum Reference unit
matches:
The choice of configu-
ration in 1-00 Configuration
Mode: for [1] Speed closed
, the
S
2
h
Function:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VLT FC 300 and is the answer not in the manual?

Table of Contents