Ac Mains Connection; Control Wiring; Access - Danfoss VLT AutomationDrive Operating Instructions Manual

Frequency converter
Hide thumbs Also See for VLT AutomationDrive:
Table of Contents

Advertisement

Installation
Follow motor manufacturer wiring requirements
Illustration 2.8 represents mains input, motor, and earth
grounding for basic frequency converters. Actual configu-
rations vary with unit types and optional equipment.
2
2
Illustration 2.8 Example of Motor, Mains and Earth Wiring

2.4.4 AC Mains Connection

Size wiring based upon the input current of the
frequency converter. For maximum wire sizes see
10.1 Power-dependent Specifications.
Comply with local and national electrical codes for
cable sizes.
Connect 3-phase AC input power wiring to
terminals L1, L2, and L3 (see Illustration 2.8).
Depending on the configuration of the equipment,
input power will be connected to the mains input
terminals or the input disconnect.
Ground the cable in accordance with grounding
instructions provided in 2.4.2 Earth (Grounding)
Requirements
All frequency converters may be used with an
isolated input source as well as with ground
reference power lines. When supplied from an
isolated mains source (IT mains or floating delta) or
TT/TN-S mains with a grounded leg (grounded
delta), set 14-50 RFI Filter to OFF. When off, the
internal RFI filter capacitors between the chassis
and the intermediate circuit are isolated to avoid
damage to the intermediate circuit and to reduce
earth capacity currents in accordance with IEC
61800-3.
14
®
VLT
AutomationDrive Operating
Instructions

2.4.5 Control Wiring

2.4.5.1 Access

Illustration 2.9 Control Wiring Access for A2, A3, B3, B4, C3 and C4
Enclosures
Illustration 2.10 Control Wiring Access for A4, A5, B1, B2, C1 and C2
Enclosures
Please see Table 2.2 before tightening the covers.
®
MG.33.AJ.02 - VLT
is a registered Danfoss trademark
Isolate control wiring from high power
components in the frequency converter.
If the frequency converter is connected to a
thermistor, for PELV isolation, optional thermistor
control wiring must be reinforced/double
insulated. A 24 VDC supply voltage is
recommended.
Remove access cover plate with a screw driver. See
Illustration 2.9.
Or remove front cover by loosening attaching
screws. See Illustration 2.10.