Status Messages
Run on ref.
Run request
Running
Speed high
Speed low
Standby
Start delay
Start fwd/rev
7
7
Stop
Trip
Trip lock
48
VLT
Instructions
Operation status
The frequency converter is running in the
reference range. The feedback value matches
the setpoint value.
A start command has been given, but the motor
is stopped until a run permissive signal is
received via digital input.
The motor is driven by the frequency converter.
Motor speed is above the value set in
4-53 Warning Speed High.
Motor speed is below the value set in
4-52 Warning Speed Low.
In Auto On mode, the frequency converter will
start the motor with a start signal from a digital
input or serial communication.
In 1-71 Start Delay, a delay starting time was set.
A start command is activated and the motor will
start after the start delay time expires.
Start forward and start reverse were selected as
functions for two different digital inputs
(parameter group 5-1*). The motor will start in
forward or reverse depending on which
corresponding terminal is activated.
The frequency converter has received a stop
command from the LCP, digital input or serial
communication.
An alarm occurred and the motor is stopped.
Once the cause of the alarm is cleared, the
frequency converter can be reset manually by
pressing [Reset] or remotely by control
terminals or serial communication.
An alarm occurred and the motor is stopped.
Once the cause of the alarm is cleared, power
must be cycled to the frequency converter. The
frequency converter can then be reset manually
by pressing [Reset] or remotely by control
terminals or serial communication.