Application Set-Up Examples
S p e e d
R e f e r e n c e
S t a r t ( 1 8 )
F r e e z e r e f ( 2 7 )
S p e e d u p ( 2 9 )
S p e e d d o w n ( 3 2 )
6
6
Table 6.11 RS-485 Network Connection
CAUTION
Thermistors must use reinforced or double insulation to
meet PELV insulation requirements.
44
®
VLT
AutomationDrive Operating
Instructions
Parameters
Function
Setting
8-30 Protocol
FC*
8-31 Address
1*
8-32 Baud Rate
9600*
* = Default Value
Notes/comments:
Select protocol, address and
baud rate in the above
mentioned parameters.
®
MG.33.AJ.02 - VLT
is a registered Danfoss trademark
1-90 Motor
Thermal
Protection
1-93 Thermistor
Source
* = Default Value
Notes/comments:
If only a warning is desired,
1-90 Motor Thermal Protection
should be set to [1] Thermistor
warning.
Table 6.12 Motor Thermistor
Parameters
Function
Setting
[2] Thermistor
trip
[1] Analog
input 53