Specifications
FC 302
Max.
[kW]
prefuse
11
30 A
15-18.5
45 A
22
60 A
30
80 A
37
90 A
45
100 A
55
125 A
75
150 A
* UL compliance only 525-600 V
Table 10.13 525-690V*, Frame Sizes B and C

10.4 Connection Tightening Torques

Enclo-
200-240V 380-480/500V 525-600V 525-690V
sure
A2
0.25 - 2.2
A3
3.0 - 3.7
A4
0.25 - 2.2
A5
0.25 - 3.7
B1
5.5 - 7.5
B2
11
B3
5.5 - 7.5
0
10
B4
11 - 15
C1
15 - 22
C2
30 - 37
C3
18 - 22
C4
30 - 37
Table 10.14 Tightening of Terminals
For different cable dimensions x/y, where x ≤ 95mm
1)
84
VLT
Instructions
Bussmann
Bussmann
E52273
E4273
RK1/JDDZ
J/JDDZ
KTS-R-30
JKS-30
KTS-R-45
JKS-45
KTS-R-60
JKS-60
KTS-R-80
JKS-80
KTS-R-90
JKS-90
KTS-R-100
JKS-100
KTS-R-125
JKS-125
KTS-R-150
JKS-150
Power (kW)
0.37 - 4.0
5.5 - 7.5
0.75 - 7.5
0.37 - 4.0
0.37 - 7.5
0.75 - 7.5
11 - 15
11 - 15
18
18
11
22
22
22
11 - 15
11 - 15
18 - 30
18 - 30
30 - 45
30 - 45
55 - 75
55 - 75
30 - 75
37 - 45
37 - 45
55 - 75
55 - 75
MG.33.AJ.02 - VLT
®
AutomationDrive Operating
Recommended max. fuse
Bussmann
SIBA
E4273
E180276
T/JDDZ
RK1/JDDZ
JKJS-30
5017906-030
JJS-45
5014006-050
JJS-60
5014006-063
JJS-80
5014006-080
JJS-90
5014006-100
JJS-100
5014006-100
JJS-125
2028220-125
JJS-150
2028220-150
Mains
Motor
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
4.5
4.5
4.5
4.5
1.8
1.8
4.5
4.5
10
10
1)
1)
14/24
14/24
10
10
1)
1)
14/24
14/24
and y ≥ 95mm
2
2
.
®
is a registered Danfoss trademark
Ferraz-
LittelFuse
Shawmut
E81895
E163267/E2137
RK1/JDDZ
RK1/JDDZ
KLS-R-030
A6K-30-R
KLS-R-045
A6K-45-R
KLS-R-060
A6K-60-R
KLS-R-075
A6K-80-R
KLS-R-090
A6K-90-R
KLS-R-100
A6K-100-R
KLS-150
A6K-125-R
KLS-175
A6K-150-R
Torque (Nm)
DC
Brake
Earth
connection
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.5
1.5
3.7
3.7
3.7
3.7
1.8
1.8
4.5
4.5
10
10
14
14
10
10
14
14
Ferraz-
Shawmut
E2137
J/HSJ
HST-30
HST-45
HST-60
HST-80
HST-90
HST-100
HST-125
HST-150
Relay
3
0.6
3
0.6
3
0.6
3
0.6
3
0.6
3
0.6
3
0.6
3
0.6
3
0.6
3
0.6
3
0.6
3
0.6
3
0.6