Control Features - AEMC 1060 User Manual

Megohmmeter
Hide thumbs Also See for 1060:
Table of Contents

Advertisement

2.1 Control Features

1.
Safety terminals: "+", "G" and "-".
Next to the "-" terminal, there are 2 additional terminal contacts for the remote
control probe connection (3 contact connector).
2.
Rotary selector switch with 9 positions:
OFF - Instrument is off
MΩ - 50V - Insulation measurement (2kΩ to 200GΩ)
MΩ - 100V - Insulation measurement (4kΩ to 400GΩ)
MΩ - 250V - Insulation measurement (10kΩ to 1TΩ)
MΩ - 500V - Insulation measurement (20kΩ to 2TΩ)
MΩ - 1000V -Insulation measurement (40kΩ to 4TΩ)
400KΩ - Resistance measurement
- Continuity measurement
40Ω
SET-UP - Set-up of the megohmmeter
3.
START/STOP button
4.
Back-lit liquid crystal display
5.
6 buttons (1050) or 8 buttons (1060), each with a first and second function.
The second functions are highlighted in yellow below each button:
2nd - Selects the second function on each button
R-DAR-PI - Lets you choose the type of measurement to be performed.
Instantaneous Resistance (R), Dielectric Absorption (DAR), or Polariza-
tion Index (PI).
R(t) - Show/hide the interval values of insulation resistance, test voltage
and time-stamping, following a time-controlled test.
V/TIME - When measuring insulation, pressing this button displays the
time elapsed since the beginning of the measurement, then the exact
voltage generated. When performing resistance or capacitance measure-
ment, this button has no effect. In MR (memory recall), it displays the date
and time at which the measurement was stored, the exact test voltage
and the OBJ : TEST number.
- Activates or deactivates the "time-controlled" test mode
- Turns the display backlight ON or OFF
ALARM - Activates or deactivates the alarms programmed in SET-UP
- Selects a parameter to be modified
SMOOTH - Stops/Starts smoothing of displayed values during insulation
testing
- Increases the flashing parameter being displayed. To move
about the list of interval insulation measurements, in the R(t) function.
Megohmmeter Models 1050 /1060