Documentation of setting values
10
• Save the parameter values using either Quick Start or the DriveMonitor PC program
or
• Document parameters manually
If P052=0, only parameters that have been changed from the factory default are displayed. This makes it
relatively easy to record the changed parameters.
NOTE
In the factory setting several fault codes are masked out with P820 and must be enabled if required.
NOTE
The 1180 amp, 1660 amp and 1680 units contain a three phase fan. Although the armature circuit is phase
insensitive a check must be made to insure that the airflow in these units is from bottom to top. If the fan
direction is incorrect, swap the L1 and L2 phase wiring at incoming supply once the unit has been de-
energized. See drawings on pages 7-12 and 7-13.
NOTE
If the fan unit on the 1180 amp, 1660 amp and 1680 amp units become misaligned during shipment the fan
housing can be re-aligned by loosing the front two mounting screws and re-aligning.
Siemens Energy & Automation
SIMOREG DC Master Base Drive Panel Operating Instructions