Tests
3.1 Visual inspection
Test procedure
1. The customer selects cables or conductors by random sampling.
2. The following is inspected:
Result
The inspection is passed if the cable installation does not exhibit any deficiencies and matches
the information in the circuit diagram.
3.1.5

Cable markings

Fundamentals
A visual inspection is made to see whether cables and conductors are marked as defined in the
circuit diagram.
Test procedure
1. The customer selects cables or conductors by random sampling.
Result
The test is passed if the cable and conductor markings match what is specified in the circuit
diagram.
3.1.6

Setting values of circuit breakers, if used

Fundamentals
The circuit breaker settings are visually checked against what is specified in the circuit diagram.
Test procedure
1. The customer selects circuit breakers by random sampling.
2. The circuit breaker settings are visually checked against what is specified in the circuit
20
– Are the cables firmly connected?
– Have edge protectors been attached to sharp edges?
– Are the cables routed according to the circuit diagram?
– Are the cable end tags and conductor colors of cables and conductors marked as defined
in the circuit diagram?
diagram.
SINAMICS SL150 6SL3860 F03 F70 F98 F79 F76
Reference Manual Rev.201902141425 SL150 luftgekühlt