Binary Outputs; P770 Control Word For Binary Selectable Outputs; P777 Delay For Output Value At Binary Output 3; P778 Delay For Output Value At Binary Output 4 - Siemens 6RA70 Series Instructions Manual

Microprocessor-based converters from 15a to 1680a for variable speed dc drives
Hide thumbs Also See for 6RA70 Series:
  • Faq (4 pages)
Table of Contents

Advertisement

PNU
Description

10.39 Binary outputs

(see also Section 8, Sheet G112 of Operating Instructions 6RX1700-0AD**)
P770
Control word for binary selectable outputs
*
i001: 0
Binary selectable output at terminal 46 is not inverted
1
Binary selectable output at terminal 46 is inverted
(G112)
i002: 0
Binary selectable output at terminal 48 is not inverted
(G200)
1
Binary selectable output at terminal 48 is inverted
i003: 0
Binary selectable output at terminal 50 is not inverted
1
Binary selectable output at terminal 50 is inverted
i004: 0
Binary selectable output at terminal 52 is not inverted
1
Binary selectable output at terminal 52 is inverted
P771
Source for output value at binary output 1
*
Selection of binector to be injected at binary selectable output, terminal 46
0 = binector B0000
(G112)
1 = binector B0001
(G200)
etc.
P772
Source for output value at binary output 2
*
Selection of binector to be injected at binary selectable output, terminal 48
0 = binector B0000
(G112)
1 = binector B0001
(G200)
etc.
P773
Source for output value at binary output 3
*
Selection of binector to be injected at binary selectable output, terminal 50
0 = binector B0000
(G112)
1 = binector B0001
etc.
P774
Source for output value at binary output 4
*
Selection of binector to be injected at binary selectable output, terminal 52
0 = binector B0000
(G112)
1 = binector B0001
etc.
P775
Delay for output value at binary output 1
The logic level at the binary selectable output changes only if the internal
(G112)
signal level remains constant for the set delay period (internal signal level
(G200)
changes which do not last as long as this delay period are not switched
through to the output)
P776
Delay for output value at binary output 2
The logic level at the binary selectable output changes only if the internal
(G112)
signal level remains constant for the set delay period (internal signal level
(G200)
changes which do not last as long as this delay period are not switched
through to the output)
P777
Delay for output value at binary output 3
The logic level at the binary selectable output changes only if the internal
(G112)
signal level remains constant for the set delay period (internal signal level
changes which do not last as long as this delay period are not switched
through to the output)
P778
Delay for output value at binary output 4
The logic level at the binary selectable output changes only if the internal
(G112)
signal level remains constant for the set delay period (internal signal level
changes which do not last as long as this delay period are not switched
through to the output)
SIEMENS Energy & Automation
SIMOREG DC Master Base Drive Panel Operating Instructions
Value range
No. indices
[Unit]
Factory
Steps
setting
Type
0 to 1
Ind: 4
1
FS=0
Type: O2
All binector numbers
Ind: None
1
FS=0
Type: L2
All binector numbers
Ind: None
1
FS=0
Type: L2
All binector numbers
Ind: None
1
FS=0
Type: L2
All binector numbers
Ind: None
1
FS=0
Type: L2
0 to 10000
Ind: None
[ms]
FS=0
1ms
Type: O2
0 to 10000
Ind: None
[ms]
FS=0
1ms
Type: O2
0 to 10000
Ind: None
[ms]
FS=0
1ms
Type: O2
0 to 10000
Ind: None
[ms]
FS=0
1ms
Type: O2
See
Change
(Access /
Status)
P052 = 3
P051 = 40
Online
P052 = 3
P051 = 40
Online
P052 = 3
P051 = 40
Online
P052 = 3
P051 = 40
Online
P052 = 3
P051 = 40
Online
P052 = 3
P051 = 40
Online
P052 = 3
P051 = 40
Online
P052 = 3
P051 = 40
Online
P052 = 3
P051 = 40
Online
10-77