10.25 Oscillation

Function:
Parameters P480 to P483 define the waveshape of a rectangular signal (oscillation setpoint K0203). The value set in P480 determines the
signal level for the time period set in P481 and the value set in P482 the signal level for the time period set in P483.
Oscillation: Selected in P485. The free-running rectangular signal is switched through to the output K0208.
P480
Oscillation setpoint 1
FDS
(G128)
P481
Oscillation time 1
FDS
(G128)
P482
Oscillation setpoint 2
FDS
(G128)
P483
Oscillation time 2
FDS
(G128)
P484
Source for standard setpoint
*
Selection of connector to be injected as the output value when the
FDS
"Oscillation" function is not selected
(G128)
0 = connector K0000
1 = connector K0001
etc.
P485
Source for oscillation selection
*
Selection of binector to control activation of the "Oscillation" function
BDS
(log. "1" state = oscillation active)
(G128)
0 = binector B0000
1 = binector B0001
etc.
10.26 Definition of "Motor interface"
(see also Section 8, Sheets G185 and G186 of Operating Instructions 6RX1700-0AD**)
CAUTION!
The encoders for measurement and monitoring of the brush length, bearing condition, air flow and motor temperature must be
safely isolated from the power circuit.
P490
Selection of temperature sensor for analog monitoring of motor
*
temperature
(G185)
i001:
Temperature sensor at terminals 22 / 23:
i002:
Temperature sensor at terminals 204 / 205:
Settings:
0
No temperature sensor
1
KTY84
PTC thermistor with R=600 Ω
2
PTC thermistor with R=1200 Ω 1)
3
PTC thermistor with R=1330 Ω 1)
4
PTC thermistor with R=2660 Ω 1)
5
1) PTC thermistor according to DIN 44081 / 44082 with specified R at rated
response temperature, 1330 Ω on Siemens motors (setting 4 must be
selected). When a PTC thermistor is selected as the temperature
sensor, it is not necessary to set parameters P491 and P492 (alarm and
trip temperatures). These two temperatures are predetermined by the
type of PTC thermistor installed. Whether an alarm or fault is output
when the operating point of the PTC thermistor is reached depends on
how the relevant input is parameterized (P493.F or P494.F).
P491
Analog monitoring of motor temperature: Alarm temperature
FDS
Operative only when P490.x=1.
(G185)
SIEMENS Energy & Automation
SIMOREG DC Master Base Drive Panel Operating Instructions
1)
Value range
No. indices
[Unit]
Factory
Steps
setting
Type
-199.9 to 199.9
Ind: 4
[%]
FS=0,5
0.1% of maximum
Type: I2
speed
0.1 to 300.0
Ind: 4
[s]
FS=0.1
0.1s
Type: O2
-199.9 to 199.9
Ind: 4
[%]
FS=-0,4
0.1% of maximum
Type: I2
speed
0.1 to 300.0
Ind: 4
[s]
FS=0.1
0.1s
Type: O2
All connector
Ind: 4
numbers
FS=209
1
Type: L2
All binector numbers
Ind: 2
1
FS=0
Type: L2
0 to 5
Ind: 2
1
FS=0
Type: O2
0 to 200
Ind: 4
[°C]
FS=0
1°C
Type: O2
See
Change
(Access /
Status)
P052 = 3
P051 = 40
Online
P052 = 3
P051 = 40
Online
P052 = 3
P051 = 40
Online
P052 = 3
P051 = 40
Online
P052 = 3
P051 = 40
Offline
P052 = 3
P051 = 40
Offline
P052 = 3
P051 = 40
Offline
P052 = 3
P051 = 40
Online
10-51

Advertisement

   Also See for Siemens 6RA70 Series

   Related Manuals for Siemens 6RA70 Series

Comments to this Manuals

Symbols: 0
Latest comments:
  • Rolando Guevarra Jan 02, 2018 12:48:
    Hi, i have trouble in our drive, F019, anyone can help to solve this fault. Thanks in advance
  • vivek Kumar Jul 28, 2015 05:25:
    6ra70 drive 250 kw problem field weakning optimizati​on failed fault f050 fault valu 10 plz help... m
  • vk jadaun Jul 18, 2015 02:16:
    242 kw dc drive but problem optimizati​on fail 25 current and field fault F050 fault valu 3.... ... plz suggest...