10.40 Configuration of serial interfaces on basic converter

G-SST 1 (RS485 / RS232 on X300) (see also Section 8, Sheet G170 and Section 9 of Operating Instructions 6RX1700-0AD**)
P780
Selection of protocol for G-SST1 basic converter interface
*
0
Setting has no function
(G170)
2
USS protocol
8
for factory purposes
9
For internal factory test purposes
P781
Number of process data for G-SST1
*
When P780 = 0 or 9 is selected: Parameter is irrelevant
(G170)
When USS protocol (P780=2) is selected: Number of PZD elements
0
No process data are expected or sent in the USS protocol
1...16 Number of process data words in USS protocol (same number
applies to transmission and receipt)
The received PZD elements (1 to max. 16) are available at
connectors (K2001 to K2016) and, in some cases, bit-serially at
binectors for "internal wiring" purposes.
The PZD elements to be transmitted (1 to max. 16) are selected
in parameters P784.01 to P784.16.
P782
Length of parameter jobs for G-SST1
*
(G170)
This parameter is effective only when P780=2 (USS protocol).
0
No PKW data are expected or sent in the USS protocol.
3, 4
3 or 4 PKW data words are expected in the USS protocol and 3
or 4 PKW data words are also sent (for transmission of
parameter values).
127
Number of PKWs is determined by the telegram length
P783
Baud rate for G-SST1
*
1
300 baud
(G170)
2
600 baud
3
1200 baud
4
2400 baud
5
4800 baud
6
9600 baud
7
19200 baud
8
38400 baud
9
56700 baud
11
93750 baud
13
187500 baud
P784
Source for transmit data for G-SST1
*
Selection of connectors to be transferred as transmit data to the USS
(G170)
master via USS interface 1.
i001:
Selection for word 1
i002:
Selection for word 2
...
i016:
Selection for word 16
Applicable settings:
0 = connector K0000
1 = connector K0001
etc.
P785
Options for G-SST1
i001:
0 = Bus terminator OFF
(G170)
1 = Bus terminator ON
i002:
0 = Bit 10 of the 1
by PLC".
1 = Bit 10 of the 1
PLC", i.e. when bit 10 = 0, all other bits of the 1
as well as receive words 2 to 16, are not written to connectors
K2001 to K2016, or to binectors B2100 to B2915. All these
connectors and binectors retain their old values.
10-78
st
receive word does not function as "Control
st
receive word does function as "Control by
st
receive word,
Value range
[Unit]
Steps
0, 2, 8, 9
1
0 to 16
1
0, 3, 4, 127
1
1 to 13
1
All connector
numbers
1
0 to 1
1
SIEMENS Energy & Automation
SIMOREG DC Master Base Drive Panel Operating Instructions
No. indices
See
Factory
Change
setting
(Access /
Type
Status)
Ind: None
P052 = 3
FS=2
P051 = 40
Type: O2
Offline
Ind: None
P052 = 3
FS=2
P051 = 40
Type: O2
Offline
Ind: None
P052 = 3
FS=127
P051 = 40
Type: O2
Offline
Ind: None
P052 = 3
FS=6
P051 = 40
Type: O2
Offline
Ind: 16
P052 = 3
FS=
P051 = 40
i001: 32
Offline
i002: 167
i003: 0
i004: 33
i005-i016: 0
Type: L2
Ind: 2
P052 = 3
FS=0
P051 = 40
Type: O2
Offline