Siemens 6RA70 Series Instructions Manual page 106

Microprocessor-based converters from 15a to 1680a for variable speed dc drives
Hide thumbs Also See for 6RA70 Series:
  • Faq (4 pages)
Table of Contents

Advertisement

Fault
No.
Cause as a function of fault value
(r047.001, r949.001 or r949.009 with acknowledged error)
20
Current limit is too low
(With speed controller optimization run: Less than 30% or 45% of P100 (I A,motor ) + the armature current required for zero
speed,
With optimization run for friction moment and moment of inertia compensation: Less than 20% of P100 (I A, motor ) + the
armature current required for a steady-state speed corresponding to 10% of maximum speed)
21
Field weakening range is too wide (n act < +7% n max produces |EMF| > 54% setpoint EMF)
(setpoint EMF= K289= P101 – P100 * P110)
Possible cause:
Maximum speed setting is incorrect
Pulse encoder parameters are incorrect (P140 to P143)
Parameters for tachometer adaptation are incorrect (P741)
Setpoint EMF is not correct (P101, P100, P110)
Caution:
Even a high absolute negative actual speed value can produce an | EMF | of > 54% setpoint EMF
22
With speed controller optimization run:
With an acceleration current equaling 20% or 30% of P100 (I A, motor ) + armature current required for zero speed or
With optimization run for friction moment and moment of inertia compensation:
With an acceleration current equaling the current required to achieve a steady-state speed of 10% of maximum speed +
20% of P100 (I A, motor ), the maximum speed cannot be reached within 45s +7%
Possible cause:
Centrifugal mass is too large
Drive is blocked, heavily speed-dependent or excessively high load torque
"Active" load is attempting to maintain a certain speed
Possible remedy:
Increase P100 while the optimization run is in progress in order to raise the applied acceleration current during
optimization (during the speed controller optimization run, a maximum of 45% of I A, motor (+ armature current for zero
speed) is applied as the armature current setpoint, I A,motor (P100) can thus be increased to 2.2 times the value at
maximum without exceeding 100% I A, motor during optimization)
23
With speed controller optimization run:
With an acceleration current equaling 20% or 30% of P100 (I A, motor ) + armature current required for zero speed or
With optimization run for friction moment and moment of inertia compensation:
With an acceleration current equalling the current required to achieve a steady-state speed of 10% of maximum speed +
20% of P100 (I A, motor ), the maximum speed or 100% of setpoint EMF cannot be reached within 90s +13%
Possible cause:
Flywheel mass is too large
Drive is blocked, heavily speed-dependent or excessively high load torque
"Active" load is attempting to maintain a certain speed
Possible remedy:
Increase P100 while the optimization run is in progress in order to raise the applied acceleration current during
optimization (during the speed controller optimization run, a maximum of 45% of I A, motor (+ armature current for zero
speed) is applied as the armature current setpoint, I A,motor (P100) can thus be increased to 2.2 times the value at
maximum without exceeding 100% I A, motor during optimization)
24
With speed controller optimization run:
The actual speed does not drop to below +2% of maximum speed or to below the speed threshold n min set in P370 within 2
minutes
With optimization run for field weakening:
The actual speed does not drop to below +2% of maximum speed or to below the speed threshold n min set in P370 within
10 minutes
With optimization run for friction moment and moment of inertia compensation:
The actual speed does not drop to below +2% of maximum speed or to below the speed threshold n min set in P370 within
11 or 2 minutes
Possible cause:
Single-quadrant drive coasts to a standstill too slowly
Siemens Energy & Automation
SIMOREG DC Master Base Drive Panel Operating Instructions
Description
Further information (r047.002 to r047.016)
9-17

Advertisement

Table of Contents
loading

Table of Contents