Analog Output Terminals 18/19; Analog Output Terminals 20/21; P765 Source For Output Value At Analog Output 4; P768 Normalization Of Analog Output 4 - Siemens 6RA70 Series Instructions Manual

Microprocessor-based converters from 15a to 1680a for variable speed dc drives
Hide thumbs Also See for 6RA70 Series:
  • Faq (4 pages)
Table of Contents

Advertisement

PNU
Description
P758
Normalization of analog output 2
P
758
(G115)
=
y V
[ ]
x
100
%
x = Normalization input (corresponds to filtering output)
y = Normalization output (corresponds to output voltage at analog output
with offset = 0)
P759
Offset for analog output 2
(G115)
Analog output terminals 18 / 19
P760
Source for output value at analog output 3
*
Selection of connector whose value is to applied to the analog output
(G116)
0 = connector K0000
1 = connector K0001
etc.
P761
Mode of signal injection at analog output 3
*
0 = Injection of signal with correct sign
1 = Injection of absolute value of signal
(G116)
2 = Injection of signal with sign, inverted
3 = Injection of absolute value of signal, inverted
P762
Filtering time for analog output 3
(G116)
P763
Normalization of analog output 3
P
763
(G116)
=
y V
[ ]
x
100
%
x = Normalization input (corresponds to filtering output)
y = Normalization output (corresponds to output voltage at analog output
with offset = 0)
P764
Offset for analog output 3
(G116)
Analog output terminals 20 / 21
P765
Source for output value at analog output 4
*
Selection of connector whose value is to applied to the analog output
(G116)
0 = connector K0000
1 = connector K0001
etc.
P766
Mode of signal injection at analog output 4
*
0 = Injection of signal with correct sign
1 = Injection of absolute value of signal
(G116)
2 = Injection of signal with sign, inverted
3 = Injection of absolute value of signal, inverted
P767
Filtering time for analog output 4
(G116)
P768
Normalization of analog output 4
P
768
(G116)
=
y V
[ ]
x
100
%
x = Normalization input (corresponds to filtering output)
y = Normalization output (corresponds to output voltage at analog output
with offset = 0)
P769
Offset for analog output 4
(G116)
10-76
Value range
[Unit]
Steps
-200.00 to 199.99
[V]
0.01V
-10.00 to 10.00
[V]
0.01V
All connector
numbers
1
0 to 3
1
0 to 10000
[ms]
1ms
-200.00 to 199.99
[V]
0.01V
-10.00 to 10.00
[V]
0.01V
All connector
numbers
1
0 to 3
1
0 to 10000
[ms]
1ms
-200.00 to 199.99
[V]
0.01V
-10.00 to 10.00
[V]
0.01V
SIEMENS Energy & Automation
SIMOREG DC Master Base Drive Panel Operating Instructions
No. indices
See
Factory
Change
setting
(Access /
Type
Status)
Ind: None
P052 = 3
FS=10.00
P051 = 40
Type: I2
Online
Ind: None
P052 = 3
FS=0.00
P051 = 40
Type: I2
Online
Ind: None
P052 = 3
FS=0
P051 = 40
Type: L2
Online
Ind: None
P052 = 3
FS=0
P051 = 40
Type: O2
Online
Ind: None
P052 = 3
FS=0
P051 = 40
Type: O2
Online
Ind: None
P052 = 3
FS=10.00
P051 = 40
Type: I2
Online
Ind: None
P052 = 3
FS=0.00
P051 = 40
Type: I2
Online
Ind: None
P052 = 3
FS=0
P051 = 40
Type: L2
Online
Ind: None
P052 = 3
FS=0
P051 = 40
Type: O2
Online
Ind: None
P052 = 3
FS=0
P051 = 40
Type: O2
Online
Ind: None
P052 = 3
FS=10.00
P051 = 40
Type: I2
Online
Ind: None
P052 = 3
FS=0.00
P051 = 40
Type: I2
Online

Advertisement

Table of Contents
loading

Table of Contents