PNU
Description
P601
Source for armature current controller setpoint
*
i001,i002 Speed limiting controller:
Selection of connectors to be injected as input quantities for
(G160)
the speed limiting controller. Both values are added.
(G161)
(G162)
i003,i004 Current limitation:
Selection of connectors to be injected as armature current
controller setpoint (before current limitation). Both values are
added.
i005,i006 Current control:
Selection of which connectors are connected as the armature
current controller setpoint (before current controller). The
two values are added. The magnitude is formed from the
value selected with index 6.
Settings:
0 = connector K0000
1 = connector K0001
etc.
P602
Source for armature current controller actual value
*
Selection of connector to be injected as armature current controller
actual value
(G162)
0 = connector K0000
1 = connector K0001
etc.
P603
Source for variable current limit in torque direction I
*
i001..i004 Selection of connector to be injected as variable current limit
(G161)
in torque direction I
Normalization: +100% corresponds to P100*P171
i005
Selection of connector to be injected as current limit in torque
direction I with Fast Stop or Shutdown
Normalization: +100% corresponds to P100*P171
i006
Selection of connector to be injected as variable current limit
in torque direction I
Normalization: +100% corresponds to r072.002
[can be set in SW 1.9 and later]
i007
Selection of connector to be injected as current limit in torque
direction I with Emergency Stop or Shutdown
Normalization: +100% corresponds to r072.002
[can be set in SW 1.9 and later]
Settings:
0 = connector K0000
1 = connector K0001
etc.
10-60
Value range
[Unit]
Steps
All connector
numbers
1
[SW 1.8 and later]
All connector
numbers
1
All connector
numbers
1
SIMOREG DC Master Base Drive Panel Operating Instructions
No. indices
See
Factory
Change
setting
(Access /
Type
Status)
Ind: 6
P052 = 3
FS=
P051 = 40
i001: 141
Offline
i002: 0
i003: 134
i004: 0
i005: 125
i006: 0
Type: L2
Ind: None
P052 = 3
FS=117
P051 = 40
Type: L2
Offline
Ind: 7
P052 = 3
FS=
P051 = 40
i001: 1
Offline
i002: 1
i003: 1
i004: 1
i005: 1
i006: 2
i007: 2
Type: L2