Description
3.3 Power unit
● DC-link-side and machine-side actual current value acquisition
● Line-side and machine-side overvoltage protection with spark-gap-free metal-oxide surge
● DC link reactor for decoupling the line-side converter from the motor-side converter
● Power cables connected from below
3.3.2
Power unit components
The diagram below shows an example of the typical components of a starting converter for a
6/6-pulse drive system:
①
Circuit breaker
②
Surge suppressor
③
Line-side converter
④
Air-cooled DC link reactor, installed in a cabinet
⑤
Motor-side converter
⑥
Motor voltage sensing (U
⑦
Current transformer in the DC link
⑧
Converter transformer
⑨
Synchronizing transformer or converter
Figure 3-1
Components of a starting converter for a 6/6-pulse drive system
3.3.2.1
Design of the thyristor stack
1 or 2 thyristor stacks are used for a 6‑pulse bridge. They differ in the number of pick-offs from
the heat sinks. The thyristor stacks are equipped with various thyristors and corresponding RC
(resistor, capacitor) circuitry. Six thyristors are braced in one clamped thyristor assembly.
30
arresters
sensing)