3.3 Power unit
● DC-link-side and machine-side actual current value acquisition
● Line-side and machine-side overvoltage protection with spark-gap-free metal-oxide surge
● DC link reactor for decoupling the line-side converter from the motor-side converter
● Power cables connected from below
3.3.2

Power unit components

The diagram below shows an example of the typical components of a starting converter for a
6/6-pulse drive system:
Circuit breaker
Surge suppressor
Line-side converter
Air-cooled DC link reactor, installed in a cabinet
Motor-side converter
Motor voltage sensing (U
Current transformer in the DC link
Converter transformer
Synchronizing transformer or converter
Figure 3-1
Components of a starting converter for a 6/6-pulse drive system
3.3.2.1

Design of the thyristor stack

1 or 2 thyristor stacks are used for a 6‑pulse bridge. They differ in the number of pick-offs from
the heat sinks. The thyristor stacks are equipped with various thyristors and corresponding RC
(resistor, capacitor) circuitry. Six thyristors are braced in one clamped thyristor assembly.
30
arresters
sensing)
M
SINAMICS GL150 6SL38503UM114PA0Z
Operating Instructions Rev.201910301420 MUSTER