1. Installation
1-10
Diagnostic mode
Set the diagnostic mode with DIL switches 5 and 6:
Peripheral fault mode
Diagnostic mode 1 (M1):
– No diagnosis
– No assignment in the
image table for inputs
Diagnostic mode 2 (M2):
– With diagnosis
– Diagnosis occupies 4 bytes
at the start of the image
table for inputs
Diagnostic mode 3 (M3):
– With diagnosis
– Diagnosis occupies 2 bytes
at the end of the image
table for inputs
Diagnostic mode 4 (M4):
– With diagnosis
– Diagnosis occupies 4 bytes
at the end of the image
table for inputs
Tab. 1/4:
DIL switches 5 and 6
DIL switches 5 and 6
Festo P.BE-CPX-FB20/21-EN en 1202a
5: OFF
6: OFF
(default)
5: OFF
6: ON
5: ON
6: OFF
5: ON
6: ON