CHAPTER3 SPECIFICATIONS

This chapter describes the specifications of safety remote I/O module.

3.1 General Specifications

Table3.1 shows the general specifications of safety remote I/O module.
Item
Operating ambient temperature
Storage ambient temperature
Operating ambient humidity
Storage ambient humidity
Vibration resistance
Shock resistance
Operating atmosphere
*3
Operating altitude
Installation location
*1
Overvoltage category
*2
Pollution degree
Equipment class
*1: This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical power
distribution network and the machinery within premises.
Category II applies to equipment for which electrical power is supplied from fixed facilities. The surge voltage withstand level for up to
the rated voltage of 300V is 2500V.
*2: This index indicates the degree to which conductive material is generated in terms of the environment in which the equipment is used.
Pollution degree 2 is when only non-conductive pollution occurs. A temporary conductivity caused by condensing must be expected
occasionally.
*3: Do not use or store the programmable controller under pressure higher than the atmospheric pressure of altitude 0m. Doing so may
cause malfunction. When using the programmable controller under pressure, please consult your local Mitsubishi Electric
representative.
Table3.1 General specifications
Compliant
Under
with JIS B
intermittent
3502 and IEC
vibration
61131-2
Under
continuous
vibration
Compliant with JIS B 3502 and IEC 61131-2 (147m/s
each in 3 directions X, Y, Z by sine half-wave pulse)
Specification
0 to 55°C
-40 to 75°C
5 to 95%RH, non-condensing
Constant
Frequency
acceleration
5 to 8.4Hz
----
2
8.4 to 150Hz
9.8m/s
5 to 8.4Hz
----
2
8.4 to 150Hz
4.9m/s
2
, duration of action 11ms, 3 times
No corrosive gases
0 to 2000m
Inside a control panel
II or lless
2 or less
Class III
3.1 General Specifications
Half
Sweep count
amplitude
10 times
3.5mm
each in X, Y,
----
Z directions
1.75mm
----
----
3
- 1
1
2
3
4
5
6
7
8