6
PROCEDURES AND SETTINGS BEFORE SYSTEM
OPERATION
Parameter writing
Write the parameters set on GX Developer to the safety CPU module.
(The parameters are written to the safety remote I/O module via the safety master
module.)
Connection to CC-Link Safety system
Connect to the CC-Link Safety system with the setting saved to the nonvolatile
memory inside the module by resetting or powering the safety remote I/O module
from OFF to ON.
Confirmation of system operation
Start the safety CPU module in TEST MODE and confirm the system operation.
Start of system operation
Change the safety CPU operation mode to SAFETY MODE using GX Developer.
(From previous page)
Completed
Figure 6.1 Procedure from module installation to system operation
6.1 Procedures and Settings before System Operation
6.1.1 Procedure from module installation to system operation
For writing parameters to the
safety CPU module, refer to the
"GX Developer Version 8
Operating Manual".
For starting the safety CPU
module in TEST MODE, refer to
the "QSCPU User's Manual
(Function Explanation, Program
Fundamentals)".
For changing to SAFETY MODE
of the safety CPU module, refer to
the "QSCPU User's Manual
(Function Explanation, Program
Fundamentals)".
1
2
3
4
5
6
7
8
6
- 2