PARAMETER SETTING
(3) Output dark test pulse OFF time
This parameter is used to set the OFF pulse width used in the output dark test for
each output point.
The settings are shown in Table5.13.
34. Output dark test pulse OFF time Y0
35. Output dark test pulse OFF time Y1
36. Output dark test pulse OFF time Y2
37. Output dark test pulse OFF time Y3
When a value out of the setting range is set, an error out of the setting range of
"Output dark test pulse OFF" occurs.
For details of the error, refer to Section 9.5.
POINT
Table5.13 Settings
Parameter item
When "No Use" is set for the method of wiring of output parameter, the output dark
test selection and the output dark test pulse OFF time are ignored even if they are
set.
Setting range
Default
"400 s",
"1ms",
"400 s"
"2ms"
5.2 Parameter Details
5.2.2 Output parameter
1
2
3
4
5
6
7
8
5
- 20