Installation Environment - Mitsubishi Electric MELSEC QS SERIES User Manual

Programmable controller cc-link safety system remote i/o module
Hide thumbs Also See for MELSEC QS SERIES:
Table of Contents

Advertisement

6
PROCEDURES AND SETTINGS BEFORE SYSTEM
OPERATION

6.2.2 Installation environment

For installation environment, refer to "3.1 General Specifications".
6
- 7
6.2 Mounting and Installation
6.2.2 Installation environment
• To remove the safety remote I/O module mounted with module mounting screws,
remove the screws first and then the holding fixtures from the module.
Attempting to remove the module from the holding fixtures with the screws still
attached may damage the module and/or holding fixtures.
• When using a DIN rail, pay attention to the following:
1) Applicable DIN rail model (conforming to IEC 60715)
TH35-7.5Fe
TH35-7.5Al
2) Installation screw intervals
Tighten the screws at pitches of 20mm or less.
• When installing the safety remote I/O module to the DIN rail, press the center part
of the hook located on the bottom of the module until a click is heard.
DIN rail
Hook for DIN rail
Note:
Do not press the front face as shown below. Doing so may cause failure.
DIN rail
Figure 6.4 Installation to DIN rail
• If the mechanical power supply switch is used for the safety remote I/O module,
in rare cases it does not operate, when the excessive chattering is generated at
power-on, and safety diagnostic function operates due to the unstable status of
the input power supply voltage.
In this case, turn on power supply again.
Front face