4.3 Output Function

The safety remote I/O module has one output function: double output wiring function.
(1) Double output wiring function
This function is used to double the output wiring.
An output error can be detected immediately by verifying the status of two output
signals.
The following two double output wiring methods are available for the safety remote I/O
module. Select either method depending on the wiring with connected external safety
devices.
Set the method in the "Method of wiring of output" parameter.
For the setting of the "Method of wiring of output", refer to Section 5.2.2(1).
• Double wiring with source output and sink output
24VDC
24GDC
Figure 4.5 Double wiring with source output and sink output
• Double wiring with source output and source output
24VDC
24GDC
Figure 4.6 Double wiring with source output and source output
Source output
Y0+
Sink output
Y0-
Source output
Y0+
Source output
Y1+
MC
MC
COM-