6
PROCEDURES AND SETTINGS BEFORE SYSTEM
OPERATION
Module mounting screw (M4 screw with plain washer
finished round)
Terminal screw (M3 screw)
2-piece terminal block mounting screw (M3.5 screw)
Note: Do not attach them in any positions other than those above.
• Do not drop the safety remote I/O module or apply any strong impact to it.
• Do not remove the printed circuit board (PCB) of the safety remote I/O module
from the case.
Doing so may cause failure.
• Carefully prevent any dust or wiring chips from entering the safety remote I/O
module.
Failure to do so may cause a fire, failure, or malfunction.
• When installing the safety remote I/O module to a control panel, provide
clearance of at least 60mm between the module's top/bottom and any other
structure or component to ensure proper airflow and to make module
replacement easy.
• Install the safety remote I/O module to a flat surface.
If it is not flat, an excess force may be applied to the PCB, causing failure.
• Tighten the module mounting screws and terminal screws within the following
torque range.
Overtightening may result in damage to the screws or the module case.
Table6.1 Specified torque range
Screw
• Attach the holding fixtures to two positions as shown in Figure 6.3.
Figure 6.3 Attachment of holding fixtures
Specified torque range
0.824 to 1.110N•m
0.425 to 0.525N•m
0.680 to 0.920N•m
6.2 Mounting and Installation
6.2.1 Handling precautions
1
2
3
4
5
6
7
8
6
- 6