Qs0J65Btb2-12Dt - Mitsubishi Electric MELSEC QS SERIES User Manual

Programmable controller cc-link safety system remote i/o module
Hide thumbs Also See for MELSEC QS SERIES:
Table of Contents

Advertisement

3
SPECIFICATIONS

3.2.3 QS0J65BTB2-12DT

Item
Input specifications
*2
No. of input points
Isolation method
Rated input voltage
Rated input current
Operating voltage range
Maximum simultaneous input points
ON voltage/ON current
OFF voltage/OFF current
Input resistance
Input type
OFF
ON
Response
time
ON
OFF
Safety remote station input response
time
Voltage
Current
External
power supply
Protection function
Fuse
Wiring method for common
Common current
No. of stations occupied
No. of access to nonvolatile memory
inside module
Safety refresh response processing
time
Voltage
Current
Module
Protection function
*1
power
Fuse
Momentary power
failure period
Noise immunity
Dielectric withstand voltage
Insulation resistance
Level of protection
Weight
*1:
The power supply connected to the QS0J65BTB2-12DT must satisfy the following conditions:
(1) Reinforced insulation
SELV (Safety Extra Low Voltage): Hazardous potential part (48V or more)
(2) Compliance with the LVD (Low Voltage Directive)
(3) Output voltage within 19.2V to 28.8VDC (Ripple ratio: 5% or less.)
*2:
For the module with module technical version C, the number of input points is always 8. (The single input is not supported and two
input terminals are always used for each input.)
*3:
For module technical version A, the safety remote station input response time is 32ms or less + time of noise removal filter.
*4:
For module technical version A, the safety remote station output response time is 32ms or less.
*5:
For module technical version A, the safety refresh response processing time is 38ms.
3
- 6
3.2 Performance Specifications
3.2.3 QS0J65BTB2-12DT
Table3.4 Performance specifications of QS0J65BTB2-12DT (1/2)
8 points (double input),
16 points (single input)
Photocoupler
24VDC
Approx. 4.6mA
19.2V to 28.8VDC
(Ripple ratio: 5% or less)
100%
15VDC/2mA or more
5VDC/0.5mA or less
Approx.5.6k
Negative common (source type)
0.4ms or less (at 24VDC)
0.4ms or less (at 24VDC)
*3
11.2ms
or less + time of noise
removal filter (1ms, 5ms, 10ms, 20ms,
50ms)
60mA (24VDC, with all points ON, excepting for external load current)
External power supply overvoltage/overcurrent protection function
Module power overvoltage/overcurrent protection function
Tested by a DC-type noise simulator with noise voltage of 500Vp-p,
500VAC between all external DC terminals and ground, for 1 minute
10M
DC-input transistor-output combined module
QS0J65BTB2-12DT
No. of output points
Isolation method
Rated load voltage
Operating load voltage range
Maximum load current
Maximum inrush current
Leakage current at OFF
Max. voltage drop at ON
Protection function
Output type
OFF
ON
Response
time
ON
OFF
Safety remote station output
response time
Surge suppressor
19.2V to 28.8VDC (Ripple ratio: 5% or less)
8A (Not replaceable)
16 input points/common, 4 output points/common
(Terminal block 2-wire type)
Maximum 4A (Total of inputs and outputs)
1 station
10
times
12
*5
9.6ms
19.2V to 28.8VDC (Ripple ratio: 5% or less)
140mA or less (24VDC, with all points ON)
0.8A (Not replaceable)
10ms or less
noise width of 1 s and frequency of 25 to 60Hz.
or more between all external DC terminals and ground,
by a 500VDC insulation resistance tester
IP2X
0.67kg
Output specifications
4 points
(source + sink type)
2 points
(source + source type)
Photocoupler
24VDC
19.2V to 28.8VDC (Ripple ratio: 5% or less)
0.5A/point
1.0A, 10ms or less
0.5mA or less
1.0VDC or less
Output overload protection function
Source + sink type
Source + source type
0.4ms or less (at 24VDC)
0.4ms or less (at 24VDC)
10.4ms or less (at ON
11.2ms or less (at OFF
Zener diode
OFF),
*4
ON)

Advertisement

Table of Contents
loading

Table of Contents