Programming

4 Programming

4.1 Local Control Panel (LCP)

The frequency converter can be programmed from the LCP
or from a PC via the RS485 COM port by installing the MCT
10 Set-up Software. Refer to chapter 1.2 Additional
Resources for more details about the software.
The LCP is divided into 4 functional sections.
A. Display
B. Menu key
C. Navigation keys and indicator lights
D. Operation keys and indicator lights
1
2
1-20 Motor Power
3
A
[5] 0.37kW - 0.5HP
Setup 1
4
Status
B
Menu
6
Com.
C
10
On
7
Warn.
8
Alarm
9
Hand
D
On
13
Illustration 4.1 Local Control Panel (LCP)
A. Display
The LCD-display is illuminated with 2 alphanumeric lines.
All data is displayed on the LCP.
Illustration 4.1 describes the information that can be read
from the display.
MG18A802
Quick Guide
5
Main
Quick
Menu
Menu
11
12
OK
11
11
Off
Auto
Reset
On
14
15
Danfoss A/S © 05/2016 All rights reserved.
1
Parameter number and name.
2
Parameter value.
Set-up number shows the active set-up and the edit set-up.
If the same set-up acts as both active and edit set-up, only
that set-up number is shown (factory setting). When active
3
and edit set-up differ, both numbers are shown in the
display (set-up 12). The number flashing, indicates the edit
set-up.
Motor direction is shown to the bottom left of the display –
4
indicated by a small arrow pointing either clockwise or
counterclockwise.
The triangle indicates if the LCP is in Status, Quick Menu, or
5
Main Menu.
Table 4.1 Legend to Illustration 4.1, Part I
B. Menu key
Press [Menu] to select among Status, Quick Menu, or Main
Menu.
C. Navigation keys and indicator lights
6
Com. LED: Flashes during bus communication.
7
Green LED/On: Control section is working correctly.
8
Yellow LED/Warn.: Indicates a warning.
9
Flashing Red LED/Alarm: Indicates an alarm.
[Back]: For moving to the previous step or layer in the
10
navigation structure.
[
] [
] [►]: For navigating among parameter groups and
11
parameters, and within parameters. They can also be used
for setting local reference.
[OK]: For selecting a parameter and for accepting changes
12
to parameter settings.
Table 4.2 Legend to Illustration 4.1, Part II
D. Operation keys and indicator lights
[Hand On]: Starts the motor and enables control of the
frequency converter via the LCP.
NOTICE
[2] Coast inverse is the default option for
13
parameter 5-12 Terminal 27 Digital Input. If there is
no 24 V supply to terminal 27, [Hand On] does not
start the motor. Connect terminal 12 to terminal 27.
[Off/Reset]: Stops the motor (Off). If in alarm mode, the
14
alarm is reset.
[Auto On]: The frequency converter is controlled either via
15
control terminals or serial communication.
Table 4.3 Legend to Illustration 4.1, Part III
4
4
23

Advertisement

Table of Contents
loading