Installation
3.2 Electrical Installation
3.2.1 Electrical Installation in General
All cabling must comply with national and local regulations on cable cross-sections and ambient temperature. Copper
conductors are required. 75 °C (167 °F) is recommended.
Power [kW (hp)]
Enclosure
IP class
3x200–240 V
size
H1
IP20
0.25–1.5
(0.33–2)
H2
IP20
2.2 (3)
H3
IP20
3.7 (5)
H4
IP20
5.5–7.5 (7.5–10)
H5
IP20
11 (15)
H6
IP20
15–18.5 (20–25)
H7
IP20
22–30 (30–40)
H7
IP20
–
H8
IP20
37–45 (50–60)
Table 3.4 Tightening Torques for Enclosure Sizes H1–H8, 3x200–240 V & 3x380–480 V
Power [kW (hp)]
Enclosure
IP class
3x380–480 V
size
I2
IP54
0.75–4.0 (1–5)
I3
IP54
5.5–7.5 (7.5–10)
I4
IP54
11–18.5 (15–25)
I6
IP54
22–37 (30–50)
I7
IP54
45–55 (60–70)
I8
IP54
75–90 (100–125)
Table 3.5 Tightening Torques for Enclosure Sizes I2–I8
Power [kW (hp)]
Enclosure
IP class
3x525–600 V
size
H9
IP20
2.2–7.5 (3–10)
H10
IP20
11–15 (15–20)
H6
IP20
18.5–30 (25–40)
H7
IP20
37–55 (50–70)
H8
IP20
75–90 (100–125)
Table 3.6 Tightening Torques for Enclosure Sizes H6–H10, 3x525–600 V
1) Cable dimensions >95 mm
2
≤ 95 mm
2
2) Cable dimensions
MG18A802
Quick Guide
3x380–480 V
Mains
0.37–1.5 (0.5–2)
0.8 (7)
2.2–4.0 (3–5)
0.8 (7)
5.5–7.5 (7.5–10)
0.8 (7)
11–15 (15–20)
1.2 (11)
18.5–22 (25–30)
1.2 (11)
30–45 (40–60)
4.5 (40)
55 (70)
10 (89)
75 (100)
14 (124)
90 (125)
1)
24 (212)
24 (212)
Mains
Motor
0.8 (7)
0.8 (7)
0.8 (7)
0.8 (7)
1.4 (12)
0.8 (7)
4.5 (40)
4.5 (40)
10 (89)
10 (89)
14 (124)/24
14 (124)/24
(212)
2)
(212)
2)
Mains
Motor
1.8 (16)
1.8 (16)
1.8 (16)
1.8 (16)
4.5 (40)
4.5 (40)
10 (89)
10 (89)
14 (124)/24
14 (124)/24
2)
2)
(212)
(212)
Danfoss A/S © 05/2016 All rights reserved.
Torque [Nm (in-lb)]
Motor
DC
Control
connection
terminals
0.8 (7)
0.8 (7)
0.5 (4)
0.8 (7)
0.8 (7)
0.5 (4)
0.8 (7)
0.8 (7)
0.5 (4)
1.2 (11)
1.2 (11)
0.5 (4)
1.2 (11)
1.2 (11)
0.5 (4)
4.5 (40)
–
0.5 (4)
10 (89)
–
0.5 (4)
14 (124)
–
0.5 (4)
–
0.5 (4)
1)
Torque [Nm (in-lb)]
DC
Control
connection
terminals
0.8 (7)
0.5 (4)
0.8 (7)
0.5 (4)
0.8 (7)
0.5 (4)
–
0.5 (4)
–
0.5 (4)
–
0.5 (4)
Torque [Nm (in-lb)]
DC
Control
connection
terminals
Not
0.5 (4)
recommended
Not
0.5 (4)
recommended
–
0.5 (4)
–
0.5 (4)
–
0.5 (4)
Ground
Relay
0.8 (7)
0.5 (4)
0.8 (7)
0.5 (4)
0.8 (7)
0.5 (4)
0.8 (7)
0.5 (4)
0.8 (7)
0.5 (4)
3 (27)
0.5 (4)
3 (27)
0.5 (4)
3 (27)
0.5 (4)
3 (27)
0.5 (4)
Ground
Relay
0.8 (7)
0.5 (4)
0.8 (7)
0.5 (4)
0.8 (7)
0.5 (4)
3 (27)
0.6 (5)
3 (27)
0.6 (5)
3 (27)
0.6 (5)
Ground
Relay
3 (27)
0.6 (5)
3 (27)
0.6 (5)
3 (27)
0.5 (4)
3 (27)
0.5 (4)
3 (27)
0.5 (4)
9
3
3