Installation
3.2.4 Fuses and Circuit Breakers
Branch circuit protection
To prevent fire hazards, protect the branch circuits in an
installation - switch gear, machines, and so on - against
short circuits and overcurrent. Follow national and local
regulations.
Short-circuit protection
Danfoss recommends using the fuses and circuit breakers
listed in Table 3.7 to protect service personnel or other
equipment in case of an internal failure in the unit or a
short circuit on the DC link. The frequency converter
provides full short-circuit protection in case of a short
circuit on the motor.
Overcurrent protection
Provide overload protection to avoid overheating of the
cables in the installation. Overcurrent protection must
always be carried out according to local and national
UL
Power [kW (hp)]
3x200–240 V IP20
0.25 (0.33)
0.37 (0.5)
0.75 (1)
1.5 (2)
2.2 (3)
3.7 (5)
5.5 (7.5)
7.5 (10)
11 (15)
15 (20)
Cutler-Hammer
EGE3100FFG
18.5 (25)
22 (30)
Cutler-Hammer
30 (40)
JGE3150FFG
37 (50)
Cutler-Hammer
JGE3200FFG
45 (60)
3x380–480 V IP20
0.37 (0.5)
0.75 (1)
1.5 (2)
2.2 (3)
3 (4)
4 (5)
5.5 (7.5)
7.5 (10)
11 (15)
15 (20)
18.5 (25)
22 (30)
MG18A802
Quick Guide
Circuit breaker
Non-UL
Moeller NZMB1-
A125
Moeller NZMB1-
A160
Moeller NZMB1-
A200
Danfoss A/S © 05/2016 All rights reserved.
regulations. Circuit breakers and fuses must be designed
for protection in a circuit capable of supplying a maximum
of 100000 A
(symmetrical), 480 V maximum.
rms
UL/Non-UL compliance
To ensure compliance with UL or IEC 61800-5-1, use the
circuit breakers or fuses listed in Table 3.7.
Circuit breakers must be designed for protection in a
circuit capable of supplying a maximum of 10000 A
(symmetrical), 480 V maximum.
NOTICE
In the event of malfunction, failure to follow the
protection recommendation may result in damage to the
frequency converter.
Fuse
UL
Bussmann
Bussmann
Bussmann
Type RK5
Type RK1
Type J
FRS-R-10
KTN-R10
JKS-10
FRS-R-10
KTN-R10
JKS-10
FRS-R-10
KTN-R10
JKS-10
FRS-R-10
KTN-R10
JKS-10
FRS-R-15
KTN-R15
JKS-15
FRS-R-25
KTN-R25
JKS-25
FRS-R-50
KTN-R50
JKS-50
FRS-R-50
KTN-R50
JKS-50
FRS-R-80
KTN-R80
JKS-80
FRS-R-100
KTN-R100
JKS-100
FRS-R-100
KTN-R100
JKS-100
FRS-R-150
KTN-R150
JKS-150
FRS-R-150
KTN-R150
JKS-150
FRS-R-200
KTN-R200
JKS-200
FRS-R-200
KTN-R200
JKS-200
FRS-R-10
KTS-R10
JKS-10
FRS-R-10
KTS-R10
JKS-10
FRS-R-10
KTS-R10
JKS-10
FRS-R-15
KTS-R15
JKS-15
FRS-R-15
KTS-R15
JKS-15
FRS-R-15
KTS-R15
JKS-15
FRS-R-25
KTS-R25
JKS-25
FRS-R-25
KTS-R25
JKS-25
FRS-R-50
KTS-R50
JKS-50
FRS-R-50
KTS-R50
JKS-50
FRS-R-80
KTS-R80
JKS-80
FRS-R-80
KTS-R80
JKS-80
rms
Non-UL
Maximum
Bussmann
fuse
Type T
Type G
JJN-10
10
JJN-10
10
JJN-10
10
JJN-10
10
JJN-15
16
JJN-25
25
JJN-50
50
JJN-50
50
JJN-80
65
JJN-100
125
JJN-100
125
JJN-150
160
JJN-150
160
JJN-200
200
JJN-200
200
JJS-10
10
JJS-10
10
JJS-10
10
JJS-15
16
JJS-15
16
JJS-15
16
JJS-25
25
JJS-25
25
JJS-50
50
JJS-50
50
JJS-80
65
JJS-80
65
17
3
3