A-4
Specifications
Publication 1394-5.20 — July 2001
User-Supplied Contactor (M1)
The table below shows the requirements for the contactor that you
must supply.
The contactor:
Rating
AC Coil Operation
Recommended
types:
DC Coil Operation
1
x indicates coil voltage.
2
A surge suppressor is required.
User-Supplied Line Input Fusing
The table below shows the requirements for the input fusing that you
must supply.
The Recommended
Is:
type of fuse for:
Bussmann KTK-R-20 or
equivalent
1394C-SJT05 systems
Bussmann LPJ-SP 20 or
equivalent
Bussmann KTK-R-30 or
equivalent
1394C-SJT10 systems
Bussmann LPJ-SP 30 or
equivalent
Bussmann FRS-R-35 or
equivalent
Bussmann LPS-RK-SP 40
1394C-SJT22 systems
or equivalent
Bussmann LPJ-SP 45 or
equivalent
For the 1394C-SJT05 and
For the 1394C-SJT22 is:
1394C-SJT10 is:
600V AC, 23A
600V AC, 37A
1,2
Allen-Bradley 100-C23x10
Allen-Bradley 100-C37x10
1
Allen-Bradley 100-C23Zx10
Allen-Bradley 100-C37Zx10
Rating
600V AC, 20A
600V AC, 20A
600V AC, 30A
600V AC, 30A
600V AC, 35A
600V AC, 40A
600V AC, 45A
1,2
1