How to Configure the System
4.1.3 Commissioning
After setting the station address from VLT
AutomationDrive FC 302, cycle power on the frequency
converter to activate the new address. The master/PLC
now recognizes the frequency converter as VLT
solid green NS LED on the MCA 114 option indicates that
communication between the master and the frequency
4
4
converter is established. If the NS LED flashes, the
master/PLC has not recognised the frequency converter.
For more information, refer to 6.1 Step-by-step Trouble-
shooting
State
Power On
Baud rate search
Wait Parameterising
Wait Configuration
Data Exchange
Table 4.3 Net Status
No light
Green:
Green:
Green:
Red:
Table 4.4 Module Status ( DP-V1 Communication)
NOTICE
The LEDs flash patterns of the MCA114 are not
compatible with the patterns of the VLT
LEDs.
10
®
VLT
AutomationDrive FC 302 PROFIBUS Converter Operating Instructions
®
5000 to VLT
®
5000. A
Red:
Green:
Green:
Green:
Red:
Green:
Red:
Green:
Red:
LED
®
5000 PROFIBUS
MG34N202 - Rev. 2013-10-15
4.2 LED Behaviour
®
The option has 2 bi-coloured LEDs:
LED label
NS
MS
Table 4.2 Bi Coloured LEDs
LED
Solid red
Flashing green The option is OK.
Flashing green
Long green
flash
Long red flash
Short green
flash
Short red flash
Solid green
Flashing red
Off
No PROFIBUS DPV1 communication is active.
Short green flash
DP V1 communication from a Master Class 1
(PLC) is active.
Long green flash
DP V1 communication from a Master Class 2
(MCT 10, FDT) is active.
Solid green
DP V1 communication from a Master Class 1
and 2 is active.
Flashing red
Internal error.
Description
Network Status
Modul Status ( DP-V1 communication)
Description
The option is defect. Contact
Danfoss
Searching for the baud rate.
Check the connection to the
master if the option stays in this
state.
Baud rate found - waiting for
parameters from the master.
Wrong parameters from the
master.
Parameters from master OK –
waiting for configuration data.
Wrong Configuration data from
the master.
Data Exchange between the
master and the FC 300 is active.
Clear State. Warning 34 is active
and a bus reaction in par. 8-04 is
executed.
Description