Troubleshooting

6 Troubleshooting

6.1 Step-by-step Troubleshooting

After copying the station address from the VLT
®
the VLT
AutomationDrive FC 302, power must be cycled
to the FC 302. The master/PLC should now recognise FC
®
302 as a VLT
5000. The NS LED on the MCA 114 option
should now be solid green indicating that communication
between master and slave is established.
If the NS LED flashes, the master/PLC has not recognized
the FC 302:
Check if station address is the same in the FC 302
®
as the replaced VLT
Check 9-63 Actual Baud Rate. If the frequency
converter has a connection to the master, this
parameter displays the detected baudrate. If no
master has been detected, the parameter
displays: "No baud rate found".
Check 9-53 Profibus Warning Word.
Warn. Word
Bit
[Hex]
0
0001
Connection with DP-master is not OK
1
0002
Unused
FDL (Field-bus Data link Layer) is not
2
0004
OK
3
0008
Clear data command received
4
0010
Actual value is not updated
5
0020
Baudrate search
6
0040
PROFIBUS ASIC is not transmitting
7
0080
Initialising of PROFIBUS is not ok
8
0100
Drive is tripped
9
0200
Internal CAN error
10
0400
Wrong configuration data from PLC
11
0800
Wrong ID sent by PLC
12
1000
Internal error occurred
13
2000
Not configured
14
4000
Timeout active
15
8000
Warning 34 active
Table 6.1 Warning Word
Check 1.3 Constraints for more information on
limitations.
®
VLT
AutomationDrive FC 302 PROFIBUS Converter Operating Instructions
®
5000 to
5000.
Description
MG34N202 - Rev. 2013-10-15
6
6
43