Hirschmann RS20 User Manual page 41

Redundancy configuration industrial ethernet (gigabit-)switch
Hide thumbs Also See for RS20:
Table of Contents

Advertisement

Ring Redundancy
Note: Configure all the devices of the Fast HIPER-Ring individually. Before
you connect the redundant line, you must complete the configuration of all
the devices of the Fast HIPER-Ring. You thus avoid loops during the
configuration phase.
 Set up the network to meet your demands.
 Configure all ports so that the transmission speed and the duplex settings
of the lines correspond to the following table:
Bit rate
Autonegotiation
(automatic configuration)
Port
Duplex
Table 5:
Port settings for ring ports
 Select the Redundancy:Ring Redundancy dialog.
 Under "Version", select Fast HIPER-Ring.
 Define the desired ring ports 1 and 2 by making the corresponding
entries in the module and port fields. If it is not possible to enter a
module, then there is only one module in the device that is taken
over as a default.
Display in "Operation" field:
forwarding: this port is switched on and has a link.
blocked: this port is blocked and has a link
disabled: this port is disabled
not-connected: this port has no link
UM RedundConfig L2P
Release 8.0 05/2013
3.3 Example of a Fast HIPER-Ring
100 Mbit/s
off
on
Full
1000 Mbit/s
on
on
41