Type-Dependent Factory Settings - nvent raychem tcontrol-cont-03 Operating And Installation Manual

Compact microprocessor controller
Table of Contents

Advertisement

1.5

Type-dependent factory settings

The following tables show the type-dependent factory settings.
The standard factory settings are shown in the respective
sections of this manual.
The settings for type TCONTROL-CONT-03 are also valid for type
TCONTROL-CONT-03/COM.
The settings for type TCONTROL-CONT-03/MA are also valid for
type TCONTROL-CONT-03/COMA.
Set points (available within User level - USEr)
Parameter
Set point 1 (SP1)
Set point 2 (SP2)
Parameter level (PArA)
Parameter
Proportional
band (Pb1)
Derivative time (dt)
Reset time (rt)
Configuration level (ConF)
Parameter
Analog input (InP):
Scale low level (SCL) -50
Scale high level
(SCH)
Controller (Cntr):
Controller type
(CtYP)
Output value at
Out of Range
Manual mode
Self-optimization
Microsoft and Windows are registered trademarks of Microsoft Corporation.
1
6 | nVent.com
Factory setting for type
TCONTROL- CONT-03
5.0
0.0
Factory setting for type
TCONTROL- CONT-03
0.0
0 s
0 s
Factory setting for type
TCONTROL- CONT-03
250
1 (= 2-state ON/OFF)
100
inhibited
inhibited
TCONTROL- CONT-03/MA
5.0
0.0
TCONTROL- CONT-03/MA
10.0
80 s
350 s
TCONTROL- CONT-03/MA
-50
250
4 (= continuous
4...20 mA)
100
inhibited
inhibited