• For continuous controller only: Ensure that the function of the
output (OutP -> OutA) is configured to controller output 1 and
scaled to 0...100%.
This means:
Function (FnCt) = Controller output 1 (11)
Zero point (0Pnt) = 0
End value (End) = 100
• For modulating controllers only: Determine the actuator time
(tt) and set in the Parameter level
Start of self-optimization
1. Simultaneously press the +
In the lower display,
"tUnE" appears flashing.
Self-optimization is completed when the display automatically
changes to the standard display. The duration of self-optimization
depends on the process.
Canceling self-optimization
1. Cancel using + (simultaneously)
keys (> 2 s)
nVent.com | 45