How to Programme
A trip is the action when an alarm has appeared. The trip will stop the AFE operation and change the digital output at
terminal 27 to Low, which will result in coasting the motor. It can be reset by pressing the reset button or make a reset by
a digital input (parameter group 5-1* Digital Inputs [1]). The origin event that caused an alarm cannot damage the AFE or
cause dangerous conditions. A trip lock is an action when an alarm occurs, which may cause damage to AFE or connected
units. A Trip Lock situation can only be reset by a power cycling.
Warning
Alarm
Trip locked
Table 6.7 LED indication
Alarm Word Extended Status Word
Bit Hex
6
6
0
00000001
1
00000002
2
00000004
3
00000008
4
00000010
5
00000020
6
00000040
7
00000080
8
00000100
9
00000200
10
00000400
11
00000800
12
00001000
13
00002000
14
00004000
15
00008000
16
00010000
17
00020000
18
00040000
19
00080000
20
00100000
21
00200000
22
00400000
23
00800000
24
01000000
25
02000000
26
04000000
27
08000000
28
10000000
29
20000000
30
40000000
66
Operating Instructions
yellow
flashing red
yellow and red
Dec
Alarm Word
1
2
Heatsink temp. (A29) ServiceTrip,
4
Earth Fault (A14)
8
Ctrl.Card Temp (A65) ServiceTrip,
16
Ctrl. Word TO (A17)
32
Over Current (A13)
64
128
256
512
Inverter Overld. (A9)
1024
DC under Volt (A8)
2048
DC over Volt (A7)
4096
Short Circuit (A16)
8192
Inrush Fault (A33)
16384
Mains ph. Loss (A4)
32768
65536
131072
Internal Fault (A38)
262144
524288
1048576
2097152
4194304
Fieldbus Fault (A34)
8388608
24 V Supply Low
(A47)
16777216
Mains Failure (A36)
33554432
1.8V Supply Low
(A48)
67108864
134217728
268435456 Option Change (A67) reserved
536870912 AFE Initialized(A80)
1073741824 Safe Stop (A68)
Danfoss A/S © Rev. 05/2014 All rights reserved.
Alarm Word 2
Warning Word
ServiceTrip, Read/
Write
Heatsink temp. (W29)
(reserved)
ServiceTrip,
Earth Fault (W14)
Typecode/
Sparepart
Ctrl.Card Temp (W65)
(reserved)
ServiceTrip,
Ctrl. Word TO (W17)
(reserved)
reserved
Over Current (W13)
reserved
reserved
reserved
reserved
Inverter Overld (W9)
reserved
DC under Volt (W8)
reserved
DC over Volt (W7)
reserved
DC Voltage Low (W6)
reserved
DC Voltage High (W5)
reserved
reserved
reserved
10V Low (W1)
Fans error
reserved
reserved
reserved
Fieldbus Fault (W34)
reserved
24V Supply Low (W47)
reserved
Mains Failure (W36)
reserved
Current Limit (W59)
reserved
Low Temp (W66)
reserved
Voltage Limit (W64)
Feedback Fault
Feedback Fault (W61,
(A61, A90)
W90)
Warning
Extended
Word 2
Status Word
reserved
Ramping
reserved
reserved
reserved
reserved
reserved
reserved
reserved
reserved
Power limit (W253)
Regen limit (W252)
reserved
Password Timelock
Fans Warn
Password Protection
reserved
reserved
reserved
reserved
reserved
reserved
reserved
reserved
reserved
MG33X402

Advertisement

Table of Contents
loading

Table of Contents