Functions/operations using PROFIBUS PA
10.2 Acyclic data transfer
The "Out of service (O/S)" mode is retained after switching back to the automatic mode. The
actuator remains depressurized after a power failure.
Note
You must set the target mode to "Automatic" to reactivate the setpoints of the cyclic master.
10.2.2.16

Simulation

Register
Use this sub-menu to access the "Simulation" online menu that is split into the following four
tabs:
● Simulation of actual value
● Simulation of device status
● Simulation of device diagnostics
Simulation of actual value
You can activate the actual value simulation in this tab and also define the actual value to be
simulated and its quality and status. The following feedback values are available:
● Setpoint
● Actual value
● Setpoint deviation
● Checkback
Changes become effective as soon as the Transfer button is pressed.
Simulation of device status
You can activate simulation of the device status in this tab and then select the diagnostics
messages to be simulated. This concerns the content of the "DIAGNOSTICS physical block
parameter" that generates different diagnostics messages depending on whether the
condensed status has been activated or deactivated. Changes become effective as soon as
the Transfer button is pressed.
Simulation of device diagnostics
In this tab you enable simulation of device diagnostics.
You can then select the desired diagnostics events in the simulation of device diagnostics,
and use device diagnostics and message text to obtain the feedback indicating that the
corresponding event has been triggered in the device. Changes become effective as soon as
the Transfer button is pressed.
210
SIPART PS2 with PROFIBUS PA
Operating Instructions, 02/2016, A5E00127926-AB