Alarm, fault and system messages
11.3 Online diagnostics
11.3.2

Overview of error codes

Overview of error codes that activate the fault message output
Error
Three-
Event
code
stage
1
No
Control deviation:
Actual value re‐
sponse has excee‐
ded values for TIM
and LIM
2
No
Device not in "Au‐
tomatic" mode
3
No
Binary input BIN1
or BIN2 active
4
Yes
Limit for number of
total strokes ex‐
ceeded
5
Yes
Limit for number of
changes in direc‐
tion exceeded
6
Yes
Lower endstop lim‐
it exceeded
7
Yes
Upper endstop lim‐
it exceeded
8
No
Deadband limit ex‐
ceeded
9
Yes
Case 1: Reference
stroke time for par‐
tial stroke test is ex‐
ceeded.
Case 2: Start posi‐
tion outside the
start tolerance
268
Parameter setting
Error message disappears
when
Always active
... the actual value response
falls below the value for LIM
**. FCT
... the device is changed to
1)
"Automatic" mode.
= nA or = nAB
**. FCT
... the binary input is no longer
1)
activated.
= nAB and binary
function BIN1 or
BIN2 to "On"
L. STRK≠OFF
... the stroke counter is reset
or the thresholds are in‐
creased
O. DCHG≠OFF
... the counter for changes of
direction is reset or the thresh‐
olds are increased.
F. ZERO≠OFF
... the deviation of the endstop
disappears or the device is re-
**.YCLS = do or up
initialized.
do
G. OPEN≠OFF
... the deviation of the endstop
**.YCLS
= do or
disappears or the device is re-
1)
up do
initialized.
E. DEBA≠OFF
... the limit is undershot again
**.DEBA
= Auto
1)
A. PST≠OFF
Case 1: ... a partial stroke test
is successfully executed with‐
in the reference stroke time or
the function is deactivated.
Case 2: Move the actuator into
the range of the PST start tol‐
erance. Or increase the PST
start tolerance until the actua‐
tor (PST start position) is with‐
in the PST start tolerance.
Start the partial stroke test
again.
Possible causes
Compressed air failure, actua‐
tor fault, valve fault (e.g. block‐
ade).
The device has been config‐
ured or is in the manual mode
The contact connected to the
binary input was active (e.g.
packing gland monitoring,
overpressure, temperature
switch).
The total path covered by the
actuator exceeds one of the
configured thresholds.
The number of changes of di‐
rection exceeds one of the
configured thresholds.
Wear and tear of the valve
seat, deposits or foreign bod‐
ies in the valve seat, mechan‐
ical misalignment, friction
clutch moved.
Wear and tear of the valve
seat, deposits or foreign bod‐
ies in the valve seat, mechan‐
ical misalignment, friction
clutch moved.
Increased packing gland fric‐
tion, mechanical gap in the po‐
sition feedback.
Case 1: Valve is stuck or rus‐
ted. Increased stiction.
Case 2: Valve is present in the
safety position.
SIPART PS2 with PROFIBUS PA
Operating Instructions, 02/2016, A5E00127926-AB