'37.YCDO' Lower value for tight closing / '38.YCUP' Upper value for tight closing

Adjustment range:
Purpose:
Factory setting:
Note
The value in the parameter "YCDO" is always smaller than that in "YCUP". The tight closing
function has a fixed hysteresis of 1%. The parameters "YCDO" and "YCUP" are relative to the
mechanical stops. The parameters "YCDO" and "YCUP" are independent of the value set in
the "'6.SDIR' Setpoint direction (Page 157)" parameter.
9.3.2.11

'39.BIN1' / '40.BIN2' Function of binary inputs

Setting option
Purpose:
SIPART PS2 with PROFIBUS PA
Operating Instructions, 02/2016, A5E00127926-AB
0.0 ... 100.0
These parameters are used to set the values for "Lower value for
tight closing " (YCDO) and "Upper value for tight closing" (YCUP) in
%.
When "YCDO": 0.0
● Binary input 1
Normally open
OFF
on
bloc1
bloc2
uP
doWn
StoP
PST
● Binary input 2
Normally open
OFF
on
uP
doWn
StoP
PST
These parameters determine the function of the binary inputs. The
possible functions are described below. The direction of action can
be adapted to a normally closed or normally open mode.
● BIN1 or BIN2 = On or -On
Binary messages from peripherals, e.g. from pressure or
temperature switches, are read over the communication
interface or fed through a logical OR combination with other
messages to trigger the error message output.