Siemens SIPART PS2 Operating Instructions Manual page 48

Electropneumatic positioners with profibus pa
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

Installing/mounting
4.3 Mounting the part-turn actuator
5. Place the positioner and the mount on the actuator carefully.
6. When using the stainless steel coupling (article number TGX: 16300-1556): Place the
7. Align the positioner/mount at the center of the actuator.
8. Tighten the positioner/mount unit.
9. Initialize the positioner.
48
One of the two pins of the coupling wheel
You need not adjust the friction clutch if you use the pins
greatly simplifies commissioning. Each of the two pins
figures.
For actuators which close in the clockwise direction, use the pin on which the recess has
a V shape (B).
For actuators which open in the clockwise direction, use the pin on which the recess has
a rectangular shape (A).
Orientation of mount
Orientation of mount, flameproof enclosure
positioner and the mount on the actuator carefully. Place the stainless steel coupling on
the stump of the actuator's positioner shaft.
must fit in the carrier
as described below. This
has a recess, see the following
SIPART PS2 with PROFIBUS PA
Operating Instructions, 02/2016, A5E00127926-AB
when you do this.

Advertisement

Table of Contents
loading

Table of Contents