Adjustable Status (Condensed Status) - Siemens SIPART PS2 Operating Instructions Manual

Electropneumatic positioners with profibus pa
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

Functions/operations using PROFIBUS PA
10.3 Cyclic data transfer
The contents of the "Device status" parameter from the physical block are reported along with
the information whether a status change (event received/event sent) has occurred.
Diagnostics as per PROFIBUS DP (DDLM_Slave_Diag)
The positioner delivers the diagnostics data in the following format:
Input (master view)
Starting address
Specifier
The following specifiers are available:
1: Incoming event
2: Outgoing event
10.3.3

Adjustable status (condensed status)

Diagnostics messages are generated in the DIAGNOSTICS physical block parameter
depending on the diagnostics events in the device. At the same time, the statuses of three
PowerTags (FEEDBACK_VALUE, READBACK and POS_D) that are sent to the master by
the SIPART PS2 PA positioner are affected.
In the device, there is now an option to use diagnostics messages and predefined status
messages that are permanently associated with the triggering diagnostics events. The
condensed status must be deactivated for this purpose.
If the condensed status is activated, the diagnostics messages in a specific frame can be
allocated to a smaller number of collective diagnostics messages and selectable status
messages. This "routing" of diagnostics events is shown in the following picture.
228
0
Station_status_1
1
Station_status_2
2
Station_status_3
3
Diag_Master_Add
4
Ident_Number
5
Ident_Number
6
Header
7
Status_Type
8
Slot_Number
9
Specifier
10
Diagnostics (0)
11
Diagnostics (1)
12
Diagnostics (2)
13
Diagnostics (3)
Standard DP - diagnostics
Status coding as per DP/V1
Diagnostics object of the physical block
Operating Instructions, 02/2016, A5E00127926-AB
SIPART PS2 with PROFIBUS PA