Functions/operations using PROFIBUS PA
10.3 Cyclic data transfer
10.3.3.1

Diagnostics messages in case of deactivated condensed status

The diagnostics messages of the DIAGNOSTICS physical block parameter in case of the
deactivated condensed status are shown in the following table:
Byte
Bit
Name and meaning
0
0 ... 2
Not used
3
DIA_TEMP_ELECTR
Electronic unit temperature too
high
4
DIA_MEM_CHKSUM
Memory error
5
Not used
6
DIA_NOT_INIT
Device not initialized
7
DIA_INIT_ERR
Error in initialization
232
Cause
-
The temperature measured at the
device electronic unit has excee‐
ded one or more set thresholds.
During operation, the memory is
constantly checked for the check‐
sum and write/read errors. This
message is generated in case of
an error.
-
The initialization process re‐
quired for the device functioning
has not yet been carried out suc‐
cessfully.
Values obtained during the initial‐
ization process cannot be used.
Operating Instructions, 02/2016, A5E00127926-AB
Measure
-
Check why the temperature is be‐
yond the specified range.
Replace the electronic unit.
-
Carry out the device initialization
process.
Carry out the device initialization
process again. Check the rele‐
vant parameter settings.
SIPART PS2 with PROFIBUS PA