Diagnostic Value '17.Stic - Stiction (Slipstick); Diagnostic Value '18.Zero - Lower Endstop; Diagnostic Value '19.Open - Upper Endstop - Siemens SIPART PS2 Operating Instructions Manual

Electropneumatic positioners with profibus pa
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

Alarm, fault and system messages
11.2 Diagnostics
11.2.4.15

Diagnostic value '17.STIC - Stiction (slipstick)'

Requirement:
Display range:
Purpose:
11.2.4.16

Diagnostic value '18.ZERO - Lower endstop'

Requirement:
Display range:
Purpose:
11.2.4.17

Diagnostic value '19.OPEN - Upper endstop'

Requirement:
Display range:
Purpose:
260
Monitoring the stiction (slipstick) 'd.\\STIC' (Page 183) parameter is
activated.
● OFF
● 0.0 ... 100.0
This diagnostics parameter shows the filtered value of the slip jumps
in percent resulting from the stiction.
'50.XDIAG' Activation of extended diagnostics (Page 170) parame‐
ter is activated.
'36.YCLS' Tight closing with manipulated variable (Page 162) pa‐
rameter is set to 'do' or 'uP do'.
● OFF
● 0.0 ... 100.0
Indication of how many percent the lower endstop has changed
compared to its value during initialization. If the underlying function
is deactivated, 'OFF' is displayed.
'50.XDIAG' Activation of extended diagnostics (Page 170) parame‐
ter is activated.
'36.YCLS' Tight closing with manipulated variable (Page 162) pa‐
rameter is set to 'uP' or 'uP do'.
● OFF
● 0.0 ... 100.0
An indication of the current shift of the upper endstop compared to
its initialization value. If the underlying function is deactivated, 'OFF'
is displayed.
SIPART PS2 with PROFIBUS PA
Operating Instructions, 02/2016, A5E00127926-AB

Advertisement

Table of Contents
loading

Table of Contents