EFOY Pro 12000 Duo Operation And Installation Manual page 85

Hide thumbs Also See for Pro 12000 Duo:
Table of Contents

Advertisement

Address
30733
30735
30737
30800
Holding register (Function code 0x03)
Address
41016
41996
41998
42000
42002
42004
42006
42008
49999
Page 84
Data Interface and Optional Accessories
Name
Description
Cart21
Fill level cartridge port #2.1
Cart22
Fill level cartridge port #2.2
CartAll
Sum of the fill levels of all
connected fuel cartridges
Rev
Firmware version
Name
Description
Cartridge Reset
Reset fuel gauge of
cartridge port to 100 %.
C: Connector
DCS1: DuoCartSwitch DCS1
Modbus Address
Set Modbus address
Modbus Config
Set Modbus communication
settings.
Reset
Restart the fuel cell.
Factory Defaults
Set all parameters to
default.
Hybrid
Deactivate all parameters
for 15 seconds.
Plain text
Switch device to plain text
Protocol
interface.
Level converter
Set data interface: Front
select
side RS232, back side RS385
IDSTATESEL
Select expert setting read
property of selected ID.
See chapter 8.2.1.2
"Overview ID list" on page
87.
Unit
Multiplier
Type
l
0.001
INT32
l
0.001
INT32
l
0.001
INT32
-
1
UINT32
Value
Type
1: C#1
INT16
11: C#1 DCS1#1
12: C#1 DCS1#2
2: C#2
21: C#2 DCS1#1
22: C#2 DCS1#2
-1 : All
1 - 247
INT16
0: 9600 8,E,1
INT16
1: 9600 8,O,1
2: 9600 8,N,2
3: 9600 8,N,1
-
INT16
-
INT16
-
INT16
-
INT16
INT16
0: RS232
1: RS485
0: Actual value
INT16
1: Standard value
2: Min. value
3: Max. value